A.i. 0
: Zero tare function: brings the analogue input to 0.
M.reS.
: Allows the reset of the output if manual reset is active for the alarms and for the command
outputs;
t.1.r u n
: If timer 1 is enabled (par. 328 t m r.1 different from di s a b .), with digital input active, the timer
is switched to RUN, otherwise is kept in STOP;
t.1.s. e.
: If timer 1 is enabled (par. 328 t m r.1 different from di s a b .), acting on the digital input, the
status of the timer switches from STOP to RUN e vice versa;•
t .1 . s t a . : If il timer 1 is enabled (par.
328
t m r.1 differnet from di s a b .), acting on the digital input, the timer is switched to RUN;
t.1.e n d.
: If il timer 1 is enabled (par. 328 t m r.1 differnet from di s a b .), acting on the digital input, the
timer is switched to STOP;
t.2.r u n
: If timer 2 is enabled (par. 331 t m r.2 different from di s a b .), with digital input active, the timer
is switched to RUN, otherwise is kept in STOP;
t. 2.s. e.
: If timer 2 is enabled (par. 331 t m r. 2 different from di s a b .), acting on the digital input, the
status of the timer switches from STOP to RUN e vice versa;
t.2.s t a.
: If timer 2 is enabled (par. 331 t m r.2 different from di s a b .), acting on the digital input, the
timer is switched to RUN;
t.2.e n d.
: If timer 2 is enabled (par. 331 t m r.2 different from di s a b .), acting on the digital input, the
timer is switched to STOP;
Lo.cfG.
: With digital input active, the access to setpoint configuration/modification is locked;
u p. k e y
: simulate button
operation;
d o w n.k.
: simulate button
operation;
fnc. k.
: simulate button FNC operation;
s et. k.
: simulate button SET operation;
EXT.A L.
: External Alarm. The controller goes to STOP and the alarms are disabled. To return to START
condition, one of following events is required:
- switching off and on the controller
- activation of the digital input if the relative parameter is
st./S t.
- by pressure SET button if par. 286 s.k.s.f. set on
st./S t.
- START by serial commad on word modbus 1214).
7.7 Automatic / Manual regulation for % output control
This function allows to switch from automatic functioning to manual command of the output
percentage.
With par. 48
A . m a .1 . it is possible to select two modes.
1 First selection (
enab.) allows to eneble with FNC the writing p.--- on display 1, while on display 2 is
showed
autom.
Press SET to visualize manu.; it’s now possible, during the process visualization, modify through the
keys
c
and
d
the output percentage. To back to automatic, with the same procedure, select autom.
on display 2: immediately led MAN switches off and functioning backs to automatic.
2 Second selection (
en.sto.) enables the same functioning but with two important variants:
If there is a temporary power failure or after switch-off, the manual functioning as well as the
previous output percentage value will be maintained at restarting.
If the sensor breaks during automatic functioning, the controller switches to manual mode while
maintaining the output percentage command unchanged as generated by the PID immediately
before breakage.
Ex: on an extruder the command in percentage of the resistance (load) is maintained also in case of
input sensor failure.