40
ncoming data COM1 (def.20ms)
Delay answer/wait incoming data
(def. 20ms)
Delay answer/wait incoming data
(def. 0ms)
With slave protocol this word defines min. delay
between end of data receiving from master device and
the start of answer transmission form PL260 (max.
100ms).
With master protocol this word define max. waiting
between start of query transmission from PL260 and
full receiving of answer from slave device.
Value is expressed in ms.
R/W
new master transmission COM1 (default 5 ms)
Delay new master transmission
(default 5 ms)
Delay new master transmission
(default 5 ms)
With master protocol this word defines min. waiting
between end of data receiving (from slave to master),
and start of transmission for a new query from master
to slave.
With slave protocol this value is not used.
Value is expressed in ms, range 0-100 ms.
R/W
Number of errors for signal on status
(def. 10)
Number of errors for signal on status
(def. 10)
Number of errors for signal on status
(def. 10)
Value entered for this word defines:
If master protocol - the number of consecutive
communication errors after which the anomaly is
notified in the relevant bit of “serial status”.
If slave protocol - the time in seconds after that the
anomaly is notified keeping to "1" all bit of the word
"serial status".
R/W