EasyManua.ls Logo

Pixsys PL260 - Page 40

Pixsys PL260
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40
SM103
1103
Delay answer/wait i
ncoming data COM1 (def.20ms)
SM113
1113
Delay answer/wait incoming data
EXP1
(def. 20ms)
SM123
1123
Delay answer/wait incoming data
COM2
(def. 0ms)
With slave protocol this word defines min. delay
between end of data receiving from master device and
the start of answer transmission form PL260 (max.
100ms).
With master protocol this word define max. waiting
between start of query transmission from PL260 and
full receiving of answer from slave device.
Value is expressed in ms.
R/W
SM104
1104
Delay
new master transmission COM1 (default 5 ms)
SM114
1114
Delay new master transmission
EXP1
(default 5 ms)
SM124
1124
Delay new master transmission
COM2
(default 5 ms)
With master protocol this word defines min. waiting
between end of data receiving (from slave to master),
and start of transmission for a new query from master
to slave.
With slave protocol this value is not used.
Value is expressed in ms, range 0-100 ms.
R/W
SM105
1105
Number of errors for signal on status
COM1
(def. 10)
SM115
1115
Number of errors for signal on status
EXP1
(def. 10)
SM125
1125
Number of errors for signal on status
COM2
(def. 10)
Value entered for this word defines:
If master protocol - the number of consecutive
communication errors after which the anomaly is
notified in the relevant bit of “serial status”.
If slave protocol - the time in seconds after that the
anomaly is notified keeping to "1" all bit of the word
"serial status".
R/W

Table of Contents

Related product manuals