Function Prog.
no.
Level
1)
Standard value
2nd phase on 603 Eu --:-- (h/min)
2nd phase off 604 Eu --:-- (h/min)
3rd phase on 605 Eu --:-- (h/min)
3rd phase off 606 Eu --:-- (h/min)
Copy? 615 Eu
Default values
No | Yes
616 Eu No
Holidays heating circuit 1
Preselection
Period 1 ... 8
641 E Period 1
Start 642 E --.-- (day. month)
End 643 E --.-- (day. month)
Operating level
Frost protection | Reduced
648 E Frost Protection
Holidays heating circuit 2
Parameter only visible, if heating circuit 2 exists!
Preselection
Period 1 ... 8
651 Eu Period 1
Start 652 Eu --.-- (day. month)
End 653 Eu --.-- (day. month)
Operating level
Frost protection | Reduced
658 Eu Frost Protection
Holidays heating circuit 3
Parameter only visible, if heating circuit 3 exists!
Preselection
Period 1 ... 8
661 Eu Period 1
start 662 Eu --.-- (day. month)
End 663 Eu --.-- (day. month)
Operating level
Frost protection | Reduced
668 Eu Frost Protection
Heating circuit 1
Comfort setpoint 710 Eu 20.0°C
Reduced setpoint 712 Eu 18.0°C
Frost protection setpoint 714 Eu 10.0°C
Heating curve slope 720 Eu 1.50
Heating curve displacement 721 E 0.0 °C
Heating curve adaption
Off | On
726 E Off
Summer/winter heating limit 730 Eu 18°C
24-hour heating limit 732 E 0 °C
Flow temp setpoint min 740 E 8°C
Flow temp setpoint max 741 E 80°C
Flow temp setpoint room stat 742 E --- °C
Programming