Function Prog.
no.
Level
1)
Standard value
Delayed heat request 746 E 0 s
Room influence 750 C - - - %
Room temp limitation 760 E 0.5°C
Boost heating 770 E --- °C
Quick setback
Off | Down to reduced setpoint | Down to frost prot setpoint
780 E Down to reduced set-
point
Optimum start control max 790 E 0 min
Optimum stop control max 791 E 0 min
Reduced setp increase start 800 E --- °C
Reduced setp increase end 801 E - 15°C
Overtemp prot pump circuit
Off | On
820 E Off
Mixing valve boost 830 E 5°C
Actuator running time 834 E 120 s
Floor curing function
Off | Functional heating | Curing heating | Functional/curing heating |
Curing/Functional heating | Manually
850 E Off
Floor curing setp manually 851 E 25°C
Floor curing setp current 855 E --- °C
Floor curing day current 856 E 0
Excess heat draw
Off | Heating mode | Always
861 E Heating mode
With prim contr/system pump
No | Yes
872 E yes
Pump speed reduction
Operating level | Characteristic
880 E Characteristic
Pump speed min 882 C 30 %
Pump speed max 883 C 80 %
Curve readj at 50% speed 888 E 10 %
Flow setp readj speed ctrl
No | Yes
890 E No
Operating level changeover
Frost protection | Reduced | Comfort
898 E Reduced
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
900 E Protection
Heating circuit 2
Parameter only visible if heating circuit 2 is installed.
Comfort setpoint 1010 Eu 20.0°C
Reduced setpoint 1012 Eu 18.0°C
Frost protection setpoint 1014 Eu 10.0°C
Heating curve slope 1020 Eu 1.50
Heating curve displacement 1021 E 0.0 °C
Heating curve adaption
Off | On
1026 E Off
Programming
7308272-03 03.14 Paramount three 30-115 kW 55