Model Paramount three 30 40 60 80 95 115
Heating water
Adjustment range heating water temper-
atur
°C 20 - 85
Max. temp °C 100
Operating pressure min. bar 1,0
MPa 0,1
max. bar 3,0 4,0
MPa 0,3 0,4
Hydraulic resistance
Flow rate @20K kg/h 1254 1583 2150 3311 4085 4945
Hydraulic resistance @20K kPa 10,4 14,7 6,8 8,5 12,5 17,8
Flow rate @11K kg/h 2280 2879 4535 6020 7427 8991
Hydraulic resistance @11K kPa 26,1 37,0 26,9 25,9 38,6 55,9
Gas-connected loads
Supply pressure for natural
gas
mbar min. 18 - max. 25
Connected loads Natural gas
[H
UB
9,45 kWh/m³]
m³/h 0,59-3,20 0,95-4,00 1,48-6,10 2,22-8,10 2,12-10,1
0
2,65-12,20
Supply pressure for propane mbar min. 42,5 - max. 57,5
Propane
[H
U
12,87 kWh/kg]
kg/h 0,44-2,33 0,70-2,95 1,09-4,51 1,63-5,98 2,33-7,38 2,72-8,94
Propane
[H
U
24,64 kWh/m³]
m³/h 0,23-1,22 0,37-1,54 0,57-2,35 0,85-3,13 1,22-3,86 1,42-4,67
Electrical power consumption
Electrical connec-
tion
V/Hz 230 V / 50 Hz
max. electr. power consumption W 55 70 100 108 170 200
Heating mode protective mode W 3 3 3 3 3 3
Dimensions
Boiler weight kg 53 53 61 72 84 84
Boiler water con-
tent
l 3,6 3,6 4,7 5.8 7,8 7,8
Height mm 852
Width mm 480
Depth mm 407 407 447 542 570 570
Connections
Gas connection 3/4" 1"
Heating flow 1" 1 1/2"
Heating return 1" 1 1/2"
Technical Data Paramount Three 30-115
14 Paramount three 30-115 kW 7308272-03 03.14