(top right of ISR Plus).
5.
Set the required nominal room temperature on the rotating knob of the control
unit
6.3 Temperatures for heating
and drinking water
The information in the section Programming for setting the temperatures for heat-
ing and drinking water.
For DHW heating a setting between 50 and 60°C is recommended.
Note:
The times for DHW will be set in time programme 4/ TWW. For reasons of
comfort, the start of DHW heating should be approximately 1 hour before start of
heating!
6.4 Individual time programme
The gas boiler can be commissioned having its standard time values.
For setting e.g. an individual time programme, please observe section Time pro-
gram in Programming.
6.5
Programming of necessary
parameters
Normaly, the parameters of the control do not need to be modified (Application
example). Only date/time and possibly time programmes need to be set.
Note:
Setting of the parameters is described in the section programming.
6.6 Emergency operation
(Manual operation)
6.6.1 Set emergency operation
• Press OK button
• Select menu point maintenance/service
• Set function manual operation (prog. no. 7140) to "ON"
Heating circuit pumps have been switched on and mixer is set to manual opra-
tion
6.6.2
Adjusting setpoint manual control
Using the operation mode "manual operation" you can choose a nominal tempera-
ture value for it:
Commissioning
40 Paramount three 30-115 kW 7308272-03 03.14