Function Prog.
no.
Level
1)
Standard value
Optg mode changeover
None | Protection | Reduced | Comfort | Automatic
1500 E Protection
DHW
Nominal setpoint 1610 Eu 55°C
Reduced setpoint 1612 E 45°C
Release
24h/day | Time programs HCs | Time program 4/DHW
1620 Eu Time program 4/DHW
Charging priority
Absolute | Shifting | None | MC shifting, PC absolute
1630 E MC shifting, PC absolute
Legionella function
Off | Periodically | Fixed weekday
1640 E Fixed weekday
Legionella funct periodically 1641 E 7
Legionella funct weekday
Monday | Tuesday | Wednesday | Thursday | Friday | Saturday | Sun-
day
1642 E Sunday
Legionella funct time 1644 E - - -
Legionella funct setpoint 1645 E 65°C
Legionella funct duration 1646 E - - - min
Legionella function circ pump
Off | On
1647 E On
Circulating pump release
Time programme 3 / HCP | DHW release | Time programme 4/DHW |
Time program 5
1660 C DHW release
Circulating pump cycling
Off | On
1661 C On
Circulation setpoint 1663 E 55°C
Optg mode changeover
None | Off | On
1680 E Off
Consumer circuit 1
Flow temp setp cons request 1859 C 70°C
DHW charging priority
- No | Yes
1874 E Yes
Excess heat draw
- Off | On
1875 E ON
With buffer storage tank
- No | Yes
1878 E Yes
With prim contr/system pump
- No | Yes
1880 E Yes
Consumer circuit 2
Flow temp setp cons request 1909 C 70°C
DHW charging priority
No | Yes
1924 E Yes
Excess heat draw
Off | On
1925 E ON
With buffer storage tank
No | Yes
1928 E Yes
Programming
58 Paramount three 30-115 kW 7308272-03 03.14