Function Prog.
no.
Level
1)
Standard value
Temp differential max 2316 C ---
Temp differential nominal 2317 C 15°C
Pump modulation
None | Demand | Boiler setpoint |Temp differential nominal | Burner
output
2320 E Demand
Pump speed min 2322 E 10%
Pump speed max 2323 E 100%
Output nominal 2330 E Paramount Three 30: 28
kW
Paramount Three 40: 38
kW
Paramount Three 60: 50
kW
Paramount Three 80: 70
kW
Paramount Three 95: 90
kW
Paramount Three 115:
110 kW
Output basic stage 2331 E Paramount Three 30: 6
kW
Paramount Three 40: 9
kW
Paramount Three 60: 12
kW
Paramount Three 80: 17
kW
Paramount Three 95: 20
kW
Paramount Three 115: 25
kW
Output at pump speed min 2334 E 0%
Output at pump speed max 2335 E 100%
Max fan output heating operation 2441 E Paramount Three 30: 28
kW
*)
Paramount Three 40: 38
kW
*)
Paramount Three 60: 50
kW
*)
Paramount Three 80: 70
kW
*)
Paramount Three 95: 90
kW
*)
Paramount Three 115:
110 kW
*)
Programming
60 Paramount three 30-115 kW 7308272-03 03.14