SD300 – PROFINET
POWER ELECTRONICS
24
PARAMETERS CONFIGURATION
Code
Parameter Name
Value
Description
dr
drv / Control mode
1
1 Remote
Selects the command source for the SD300 drive.
Set the parameter to [4 COMMS] to set PROFInet
communication as the frequency reference
source.
OPT.
DESCR.
FUNCTION
0
LOCAL
Drive is controlled from the
keypad.
1
REMOTE
Commands are sent from the
control terminals.
2
REMOTE
2
Commands are sent from the
control 2 terminals.
3
MODBUS
The drive is controlled
through the communications
bus, integrated in the
equipment.
4
COMMS
The drive control is carried
out by the use of any of the
optional communication
boards.
5
PLC
The common area can be
linked with the user
sequence output and can be
used as command.