EasyManua.ls Logo

Power Electronics VS65 Series - 1 Introduction

Power Electronics VS65 Series
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
POWER ELECTRONICS
VS65
INTRODUCTION
11
1. INTRODUCTION
This chapter will introduce the VS65 Medium and High voltage solid starter series, describing their
appearance, functions and operations. We recommend that new users read this chapter and acquire an
overall understanding before operating the soft starter.
1.1. Overview
A complete VS65 includes: main circuit-breaker, control transformer, control module, silicon
controlled module, motor protecting module, and high-voltage vacuum bypass contactor. The soft
starting part includes: control module, control transformer, silicon controlled module, and high-voltage
vacuum bypass contactor.
1.2. Technical Indicators and Performance
Input voltage
2300VAC, 3300VAC, 4160VAC, 6600VAC, 10 ~ 15kVAC (-10% to +10%)
Insulation voltage
6900V, 9900V, 12500V, 19500V, 30000 ~ 45000V
Input frequency
50 ~ 60Hz ±2Hz (Automatic selection)
INPUT
Control voltage 220VAC, 50Hz
Motor output voltage
2300VAC, 3300VAC, 4160VAC, 6600VAC, 10 ~ 15kVAC (-10% to +10%)
Output frequency
50 ~ 60Hz ±2Hz
OUTPUT
Efficiency (at full load) > 99.6%
Overload capacity 125% of nominal value continuously
100% to 500% ( for 1 ~ 60s adjustable )
Main circuit components 6SCRS, 12SCRS, 18SCRS and 30SCRS (depending on rating)
SCR Peak reverse voltage
6900V ~ 39000V (depending on rating)
Phase sequence Capacity of working under any phase sequence
Transient over voltage protection dV/dt absorption network
Cooling For equipments smaller than 400A, natural cooling
For equipments bigger than 400A, cooling fan must be used
Bypass Contactor The contactor has enough capacity to start the motor directly.
Vacuum contactor if no special requirement
GENERAL DATA
SCR Trigger Power Supply 110VAC power supply for the trip circuit of SCR
Protection degree IP4x
Operation temperature -20ºC to +50ºC
Storage temperature -25ºC to +55ºC
Humidity
5% ~ 95%, non condensing
ENVIRONMENTAL
CONDITIONS
Altitude 2000m ( > 2000m ask for availability)
4 Digital Inputs ( Remote Start, Stop, Emergency Stop, DCS start / stop)
INPUTS
PTC input (optional)
3 Digital Outputs (250VAC, 5A). Configured as:
- 1 Programmable interlock relay
- 1 Bypass relay
- 1 Fault relay
OUTPUTS
1 Analogue Output 4 – 20mA proportional to output current
RS485 port as standard, RS232 and RS422 port as optional
Standard Modbus-RTU protocol
COMMUNICATIONS
Profibus (optional)
Type Removable
Length 300 mm
Connection Terminal connector
Alphanumeric Display LCD, 2 lines of 16 characters
Visualization Leds LED 1: Run
LED 2: Warning
LED 3: Power supply
LED 4: Bypass
LED 5: Communication Bus Fault
CONTROL PANEL
Keypad 6 control keys for programming, start and stop/reset.

Other manuals for Power Electronics VS65 Series

Related product manuals