Specifications
30
Powerware
®
5105 User’s Guide S 05146193 A Uncontrolled Copy
Table 9. Battery Run Times (in Minutes)
UPS Models by VA Ratings
Load (VA) 450 700 1000 1500
100 46 63 131 224
250 14 24 37 95
300 11 18 30 75
450 5 12 19 38
600 7 14 30
700 5 11 26
850 8 21
1000 7 16
1250 12
1500 8
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.