EasyManua.ls Logo

Powerware Prestige 6000 - PPDM Outlets and Input and Output Cords; Electrical Specifications for the Prestige 6000 with PPDM

Default Icon
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Specifications
67
Powerware
®
PrestigeSeriesInstallationand Operator’s ManualforIBM Applications (6000 VA)Uncontrolled Copy
PPDM Outlets and Input and Output Cords
PPDM Model Outlets InputCords OutputCords
L6-30R/IEC 320-C19 PPDM L6-30R (1)
IEC 320-C19 (1)
6-15R (2)
5-15R (8)
Detachable 2-meter cord with
L6-30R and L6-30P
IEC 320-C13/5-15P (1)
IEC 320-C13/6-15P (2)
IEC 320-C19/C20 (1)
IEC 309 PPDM IEC 309 (1)
IEC 320-C13 (6)
IEC 320-C19 (1)
Connected cord with IEC 309
(3-pin 32A)
IEC 320-C13/C14 (3)
IEC 320-C19/C20 (1)
L6-30R/5-15R PPDM L6-30R (2)
5-15R (8)
Detachable 2-meter cord with
L6-30R and L6-30P
Electrical Specifications for the Prestige 6000 with PPDM
Use the following tables to determine load wiring requirements when
the PPDM is used with the UPS. The distribution of your load on the
available outputs of the PPDMmay affect the maximum load obtainable.
Prestige 6000 PPDM Ratings with a Model 6000 UPS
PPDM Model InputUtility Voltage
and SelectedUPS
OutputVoltage
Input
Current
OutputVoltage and
MaximumCurrent
MaximumOutput
ApparentPower**
208:120/208
L6-30R/IEC 320-C19 PPDM
208 Vac 24A 120/208 Vac,
15.0/25.0A
5200 VA
208:120/208
L6-30R/5-15R PPDM
208 Vac 24A 120/208 Vac,
15.0/25.0A
5200 VA
240:240
IEC 309 PPDM
220 - 240 Vac 24A 220 - 240 Vac,
15.0/24.7A
5800 VA
240:120/240
L6-30R/5-15R PPDM
200 - 240 Vac 24A 100 - 120/200 - 240 Vac,
15.0/24.7A
5800 VA
*
Ratings based on 4000W load on PPDM, plus sufficient linear inductive load to achieve the current rating of the input
plug, not to exceed VA rating of PPU.
NOTE
Input and output currents are approximately the same when load is powered through bypass.

Related product manuals