65
Powerware
®
PrestigeSeriesInstallationand Operator’s ManualforIBM Applications (6000 VA)Uncontrolled Copy
CHAPTER 6
SPECIFICATIONS
Prestige 6000 Specifications
The following model specifications assume:
:
88% efficiency at full load (Normal mode)
:
Input power factor of 0.95
:
84% efficiency running on battery
Model6000 UPS (Nominal Operating Specifications)
OutputVA Output
Voltage
Output
Watts
InputCurrent OutputCurrent Normal
(BTUs/hr)
On Battery
(BTUs/hr)
5000 200 3350 19.6A 25.0A < 1600 < 2200
5200 208 3500 19.7A 25.0A < 1600 < 2300
5500 220 3700 19.7A 25.0A < 1700 < 2400
5750 230 3850 19.6A 25.0A < 1800 < 2500
6000 240 4000 19.5A 25.0A < 1900 < 2600
Model6000 UPS with PPDM (Nominal Operating Specifications)
OutputVA
(PPU)
OutputVoltage
(PPU)
Output Watts Normal(BTUs/hr) OnBattery
(BTUs/hr)
5000 200 3050 < 2600 < 3200
5200 208 3200 < 2600 < 3300
5500 220 3400 < 2700 < 3400
5750 230 3550 < 2800 < 3500
6000 240 3700 < 2900 < 3600