36
Holding Register (Analogue Output) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
FTC4
FTC5
CAHV
master
CAHV
slave
CRHV
master
CRHV
slave
QAHV
master
EAHV
master
EAHV
slave
Refrigerant Error Info
[READ ONLY]
69 40070
0 = Normal
1 = Error (System)
2 = Error (Startup)
3 = Maintenance Error
9 9
9
#17
9
#17
9
#17
9
7-Segment Display Error Code
Digit 1
[READ ONLY]
70 40071 (see note ^)
9 9
7-Segment Display Error Code
Digit 2
[READ ONLY]
71 40072 (see note ^^)
9 9
Status Of Heating
[READ ONLY]
72 40073
0 = No type
1 = Heating C1
2 = Heating C2
3 = Heating C3
9
0 = No type
1 = Heating/Cooling A1, Heating/Cooling B1,
Heating/Cooling C1
2 = Heating/Cooling A2, Heating/Cooling B2,
Heating/Cooling C2
3 = Heating/Cooling A3, Heating/Cooling B3,
Heating/Cooling C3
9
Heat Pump Frequency – Master
[READ ONLY]
73 40074
Frequency value in Hz
0 = 0Hz … 255 = 255Hz
9 9 9
9
9 9
Heat Pump Frequency – Slave 1
[READ ONLY]
74 40075
Frequency value in Hz
0 = 0Hz … 255 = 255Hz
9 9 9
9
9 9
Heat Pump Frequency – Slave 2
[READ ONLY]
75 40076
Frequency value in Hz
0 = 0Hz … 255 = 255Hz
9 9 9
9
9 9
Heat Pump Frequency – Slave 3
[READ ONLY]
76 40077
Frequency value in Hz
0 = 0Hz … 255 = 255Hz
9 9 9
9
9 9
Heat Pump Frequency – Slave 4
[READ ONLY]
77 40078
Frequency value in Hz
0 = 0Hz … 255 = 255Hz
9 9 9
9
9 9
Heat Pump Frequency – Slave 5
[READ ONLY]
78 40079
Frequency value in Hz
0 = 0Hz … 255 = 255Hz
9 9 9
9
9 9
Heat Pump Frequency – Slave 6
[READ ONLY]
79 40080
Frequency value in Hz
0 = 0Hz … 255 = 255Hz
9 9 9
9
9