Input Register (Analogue Input) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
FTC4
FTC5
CAHV
master
CAHV
slave
CRHV
master
CRHV
slave
QAHV
master
EAHV
master
EAHV
slave
Tank Water Temperature 65 30066
Temperature value in ºC multiplied by 100.
(see note **)
9 9
Flow Temperature – Zone 1
(signed)
66 30067
Temperature value in ºC multiplied by 100.
(see note *)
9 9
External Water Temperature 1
(signed)
Temperature value in ºC multiplied by 100.
(see note *)
9
9
9 9
Flow Temperature – Zone 1
67 30068
Temperature value in ºC multiplied by 100.
(see note **)
9 9
External Water Temperature 1
Temperature value in ºC multiplied by 100.
(see note **)
9
9
9 9
Return Temperature – Zone 1
(signed)
68 30069
Temperature value in ºC multiplied by 100.
(see note *)
9 9
External Water Temperature 3
(signed)
Temperature value in ºC multiplied by 100.
(see note *)
9
Return Temperature – Zone 1
69 30070
Temperature value in ºC multiplied by 100.
(see note **)
9 9
External Water Temperature 3
Temperature value in ºC multiplied by 100.
(see note **)
9
Flow Temperature – Zone 2
(signed)
70 30071
Temperature value in ºC multiplied by 100.
(see note *)
9 9
External Water Temperature 2
(signed)
Temperature value in ºC multiplied by 100.
(see note *)
9
9
External Water Temperature 4
(signed)
Temperature value in ºC multiplied by 100.
(see note *)
9
Flow Temperature – Zone 2
71 30072
Temperature value in ºC multiplied by 100.
(see note **)
9 9
External Water Temperature 2
Temperature value in ºC multiplied by 100.
(see note **)
9
9
External Water Temperature 4
Temperature value in ºC multiplied by 100.
(see note **)
9