61
Input Register (Analogue Input) Applicable Unit Type
Register Name Addr
Modicon
Address
Details
FTC4
FTC5
CAHV
master
CAHV
slave
CRHV
master
CRHV
slave
QAHV
master
EAHV
master
EAHV
slave
Heat Pump Refrigerant Address
3 Run Time (hours x100)
83 30084
Value in hours multiplied by 100
0 = 0 hours
65535 = 6553500 hours
9 9
Heat Pump Refrigerant Address
4 Run Time (hours x100)
84 30085
Value in hours multiplied by 100
0 = 0 hours
65535 = 6553500 hours
9 9
Heat Pump Refrigerant Address
5 Run Time (hours x100)
85 30086
Value in hours multiplied by 100
0 = 0 hours
65535 = 6553500 hours
9 9
Heat Pump Refrigerant Address
6 Run Time (hours x100)
86 30087
Value in hours multiplied by 100
0 = 0 hours
65535 = 6553500 hours
9 9
Mixing Valve Step 87 30088
0 = Step 0
10 = Step 10
9 9
Refrigerant 1 Error Code Digit 1 88 30089 (see note ^)
9 9
Refrigerant 1 Error Code Digit 2 89 30090 (see note ^^)
9 9
Refrigerant 2 Error Code Digit 1 90 30091 (see note ^)
9 9
Refrigerant 2 Error Code Digit 2 91 30092 (see note ^^)
9 9
Refrigerant 3 Error Code Digit 1 92 30093 (see note ^)
9 9
Refrigerant 3 Error Code Digit 2 93 30094 (see note ^^)
9 9
Refrigerant 4 Error Code Digit 1 94 30095 (see note ^)
9 9
Refrigerant 4 Error Code Digit 2 95 30096 (see note ^^)
9 9