EasyManua.ls Logo

PROLiNK MASTER II Series - Page 34

PROLiNK MASTER II Series
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
BATTERY
Battery setting page
Battery Warning Voltage:
HIGH: High battery warning voltage. The setting range is 14.0V ~ 15.0V. 14.4V is default setting.
LOW: Low battery warning voltage. The setting range is 10.1V ~ 14.0V. 11.4V is default setting.
This parameter setting is related to Shutdown Voltagesetting. The setting value should be
higher than Shutdown Voltage” setting.
Shutdown Voltage: If battery voltage is lower than this point in battery mode, UPS will automatically
shut down. The setting range is 10.0V ~ 12.0V. 10.7V is default setting (This setting is only available for
long-run model)
Battery age: if battery age is beyond the setting month, then the UPS will alarm for reminding. The
factory default setting is 24 months.
Battery AH: setting battery capacity.
OTHERS
OTHERS setting page1
Auto Restart:
Enable: After “Enable” is set, once UPS shutdown occurs due to low battery and then utility
restores, the UPS will return to line mode.
Disable: After “Disable” is set, once UPS shutdown occurs and the utility restores, the UPS will
not automatically turn on.
Shutdown Delay Min: UPS will shut down in setting minutes. The countdown will start after confirming
the pop-up screen.
Restore Delay Min: UPS will automatically restart in setting minutes after the UPS shuts down.

Other manuals for PROLiNK MASTER II Series

Related product manuals