N93-586-84 Issue 04 AB Page 4 of 32 © Protec Fire Detection plc 2015
Important Notes PLEASE READ CAREFULLY
B
oth the 3500 user manual and this manual should be thoroughly read and understood before
installation and commissioning is undertaken.
The 3500 and its associated connections must be installed, commissioned and maintained by a
suitably trained, skilled and competent person.
It is assumed that the person commissioning the system is aware of Protec Fire Detection
equipment terminology and terms of reference.
This equipment must be earthed and earth continuity must be preserved on broken segments of
screened cable used anywhere in the system installation.
This equipment is not guaranteed unless installed and commissioned in accordance with
current national standards.
This equipment is not suitable as part of an I.T type power distribution system as defined in
IEC60364-3.
It is perfectly normal for sealed lead acid batteries to vent small amounts of hydrogen when
being charged. The 3500 is vented to dissipate any build up of hydrogen. The 3500 enclosure
must not be sealed in any way.
A competent person trained to undertake such work MUST carry out any internal maintenance.
There are no user serviceable parts inside the 3500. Opening the PCB housing will immediately
invalidate the warranty.
0086
BS EN 54-2:1997+A1:2006
B
S EN 54-4:1997 + A1 + A2:2006
Control / Indicating and Power Supply equipment for fire
detection and fire alarm systems for buildings
3500 Fire Alarm Control Panel
Control & Indicating:
Performance under fire conditions: Pass
Response delay (response time to fire): Pass
Operational reliability: Pass
Durability of operational reliability, Temperature resistance: Pass
Durability of operational reliability, Vibration resistance: Pass
Durability of operational reliability, Electrical stability: Pass
Durability of operational reliability, Humidity resistance: Pass
Power supply:
Performance of power supply: Pass
Durability of operational reliability, Temperature resistance: Pass
Durability of operational reliability, Vibration resistance: Pass
Durability of operational reliability, Electrical stability: Pass
Durability of operational reliability, Humidity resistance: Pass