EasyManua.ls Logo

Protec 6100 - Output Control and System Settings

Protec 6100
34 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
N93-571-87 Issue 5 NH Page 21 of 34 © Protec Fire Detection plc 2019
14.8 Disabling Alarm and Fire Link Outputs
The user can disable certain 6100 functions to suit current site conditions.
The panel alarm outputs ( loop sounders and conventional alarm outputs ) can be disabled. Doing this
means that if the panel enters the alarm condition no sounders will operate. Faults from alarm devices will
not be reported.
The fire link output may also be disabled, which will prevent the fire link from activating, or generating
faults.
Please consult the system set-up record ( appendix 1 ) before making adjustments to these
critical parts of the system. If it is unknown why the system has been configured in this way
DO NOT continue.
1. Enter the user code supplied with the system and press the
¿
key to access the menus.
2. Using the ◄ and ► keys navigate to the DISABLE OPTIONS menu and press
¿
to access the menu
(Figure 14.8).
3. Press the ▲ and ▼ keys to highlight the option to be edited ( the flashing cursor indicates which option
is currently selected )
4. Press the ◄ and ► keys to toggle the state of the highlighted option.
5. Press the
¿
key to accept the changes and return to the main menu.
Figure 14.8 Disable options display
14.9 Setting the Date and Time
The SET DATE AND TIME menu allows the user to set the current date and time used by the 6100. The time
is entered in 24-hour format and is used when time stamping alarm, fault, disablement or test events.
1. Enter the user code supplied with the system and press the
¿
key to access the menus.
2. Using the and keys navigate to the SET DATE AND TIME menu and press the
¿
key. The
currently set date and time will be displayed ( Figure 14.9 ).
3. Press the and keys to move the flashing cursor to the number to be edited, then press the
and ▼ keys to set the chosen value.
4. Press the
¿
key to save the time and date and return to the main menu.
Figure 14.9 Set Date and Time display
Set date and time
dd / mm / yy HH:MM
disable OPTIONS
ALARMS disabled
Fire link enabled
Buzzer enabled

Table of Contents