18.0 Appendix 3 6100 Operation Quick Reference Guide
18.1 Entering Access Level 2
Using the keypad enter the user code ( supplied with the control panel’s documentation ).
18.2 Returning to Access Level 1
Press the
¿
key at the EXIT MENU option.
18.3 Muting the Internal Buzzer and accepting Current Faults
From access level 2 press Mute Buzzer.
18.4 Sounding the Alarms
From access level 2 press Sound Alarms.
18.5 Silencing the Alarms
From access level 2 press Silence Alarms. A further activation will re-sound the alarms.
18.6 Resetting the 6100
Determine the cause of the alarm before resetting the panel
Ensure the cause of the alarm has been removed, and any Manual Call Points locally reset.
From access level 2 press Silence Alarms then press Reset Panel.
18.7 Testing the Indicators and Internal Buzzer
From access level 2 navigate to the TEST INDICATIONS menu then press
¿
the 6100 will perform
a full indicator test. Do not press any buttons while the test is in progress.
18.8 Setting the Date and Time
From access level 2 navigate to the SET DATE AND TIME menu then press
¿
. Enter the time and
date in 24 hour format.