4.3 Determining the Installation Position
Installation Angle Requirement
The battery can be floor-mounted and wall-mounted. The installation angle requirement
is as follows:
Do not install the battery at forward tilted, back tilted, side tilted, horizontal, or
upside-down positions.
Installation Position Requirements
Install the battery on a solid brick-concrete structure or concrete wall or floor. If other
types of walls and floors are used, they must be made of fire-retardant materials and
meet the load-bearing requirements of the equipment.
Installation Space Requirements
During installation, ensure that there are no flammable or explosive materials
around the batteries. Reserve adequate space for heat dissipation and safety
isolation.
When the battery is mounted on a wall, do not place any objects under the
battery.
When install battery, no mattery it is cabinet or rack, please insure a minimum
300mm distance space for battery set. And the distance between battery and
inverter should be less than 10 meters.