EasyManua.ls Logo

RAM DBS II - DBS Chassis Sizes D1, D2, D3, E1, E2, E3 with ABB Contactor

RAM DBS II
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RAM DBS II
Refrigeration Solid State Starter
30
TABLE 15 System Setup Menu
This menu displays the current system setup in the DBS controller.
*Indicates setting is controlled by circuit board switches on main control board.
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
_______________________________________________________________________________________________
SELECTION
PARAMETERS
DEFAULT
*Full Load Amps Motor nameplate full load current (SW1) See FLA - Starter Size Table 9
*Starting Mode Constant Current/Step Ramp (SW4) Factory set for Step Ramp - See Section 5.2.4.
*Constant Current Level 200 - 425% in 25% increments (SW2) Factory set for 250% - See Section 5.2.2.
*Ramp Time 3 - 30 Sec. in 3 sec. increments (SW3) Factory set for 6 Sec. - See Section 5.2.3.
*Bypass Time 3 - 30 Sec. in 3 sec. increments (SW3) Factory set for 11 Sec. - See Section 5.2.3.
*Starter Size DBS chassis size (B, C, D, E) (SW6) Factory set.
*Thermal Overload Protection Enable - Disable (SW4) Factory set for Enable.
*Configuration (SW4) Factory set for In-Line.
*Control Mode Display/Network (SW4) Factory set for application.
Software Version
Clear Fault History Yes - No Deletes fault history.
Clear Thermal Capacity Yes - No Resets calculated motor temperature to zero.
Load Factory Setup Yes - No Restores default set points. (See Table 13)
9.0 DBS Display Unit
StockCheck.com

Table of Contents