21
Compressor Minimum Off Time at Start Up
Specifies how long the compressor remains powered off when the controller is powered on.
Compressor Minimum On Time
Specifies the minimum time that the compressor is powered on regardless of whether the control temperature decreases to less than the Cut-Out setpoint.
Specify how long the compressor remains powered on before normal controller programming powers it off.
NOTE: The adjustment knob off position immediately powers off the compressor.
Compressor Minimum Off Time
Specifies how long the compressor remains powered off before the controller powers it on. This timer must expire and the temperature must be greater than
the Cut-In setpoint for the controller to power on the compressor.
6.2.5.6 Fault
Use the Fault tab to specify a controller’s response to an open or shorted control sensor.
Sensor Failure Mode
Select Comp. Relays fails OPEN to power off the compressor if the control sensor circuit becomes open or shorted.
Select Comp. Relays fails CLOSE to power on the compressor if the control sensor circuit becomes open or shorted.
Select Duty Cycle to power cycle the compressor using the specified duty cycle regardless of the temperature.
Compressor On Time If sensor Failed
Specify the compressor power ON portion of the duty cycle.
Compressor Off Time If sensor Failed
Specify the compressor power OFF portion of the duty cycle.
Sensor Fault Monitoring Time
Specify how long a sensor failure (open or short circuit) must exist before the controller enters failure or fault mode.