EasyManua.ls Logo

Rational LM1 Series - Gas Connection Regulations and Pressure

Rational LM1 Series
92 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10 | Gas connection for gas units
70 / 92 80.06.070_iCombi Pro-iCombi Classic_IM_V01_en-GB
10 Gas connection for gas units
This section only applies to gas units.
DANGER
Fire due to incorrect gas connection
Danger to life due to fire from an incorrect gas connection.
n
Follow local regulations of the gas supply company.
n
Check the type of gas available and the dynamic connection pressure
against the values specified on the unit.
DANGER
Permissible CO/CO
2
values exceeded
Risk of poisoning due to excessive CO/CO
2
values because of incorrect
burner settings.
n
Always perform a flue gas analysis when commissioning gas units.
n
Document the flue gas values.
n
It is recommended that the installation site be equipped with a CO gas
detector.
DANGER
Increased CO values due to wrong gas type
Risk of poisoning due to connection of wrong gas type
n
Only connect the unit to the gas type stated on the unit type plate.
n
Check the type of gas available and the dynamic connection pressure
against the values specified on the unit.
n
It is recommended that the installation site be equipped with a CO gas
detector.
10.1 Regulations for gas connection
NOTICE
Connection flow pressure exceeded
A connection flow pressure above 65 mbar [0.94 psi] will lead to the unit
malfunctioning and the gas components being damaged.
n
Adhere to the maximum connection flow pressure for natural gas of 21
mbar [0.44 psi].
n
For LPG, adhere to the maximum connection flow pressure of 37 mbar
[0.84 psi].
n
Adhere to the general maximum connection flow pressure of 65 mbar
[0.94 psi].
n
If the pressure is higher, block the gas supply to the unit and do not
commission the unit.

Table of Contents

Related product manuals