D-NET Maximum Cable Length
The maximum distance for any link is 3000 feet (900 meters) and the total length cannot exceed 15,000
feet (4600 meters).
D-NET Cable
Use 20 to 22 AWG shielded twisted pair cable for all D-NET connections. Shielded cable is recommended
to minimize problems that can arise in electrically noisy environments. In addition, shielded cable may be
necessary to prevent the network from interfering with signals on other cables in the same trunk.