EasyManua.ls Logo

Reer Mosaic Series - Profinet (Mbep); Process Data Mapping

Reer Mosaic Series
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Mosaic fieldbus modules Addendum1
26/09/2018 V1.0 28/32
PROFINET (MBEP)
Process data mapping
Module Fieldbus input
Byte offset
Data direction1
Size
Name
0
In
UINT8
Fieldbus input byte 0
1
In
UINT8
Fieldbus input byte 1
2
In
UINT8
Fieldbus input byte 2
3
In
UINT8
Fieldbus input byte 3
Module System I/O
Byte offset
Data direction
Size
Name
0
Out
UINT8
System status
1
Out
UINT8
Reserved
2
Out
UINT8
Input status byte 0
3
Out
UINT8
Input status byte 1
4
Out
UINT8
Input status byte 2
5
Out
UINT8
Input status byte 3
6
Out
UINT8
Input status byte 4
7
Out
UINT8
Input status byte 5
8
Out
UINT8
Input status byte 6
9
Out
UINT8
Input status byte 7
10
Out
UINT8
Input status byte 8
11
Out
UINT8
Input status byte 9
12
Out
UINT8
Input status byte 10
13
Out
UINT8
Input status byte 11
14
Out
UINT8
Input status byte 12
15
Out
UINT8
Input status byte 13
16
Out
UINT8
Input status byte 14
17
Out
UINT8
Input status byte 15
18
Out
UINT8
Fieldbus input byte 0 feedback
19
Out
UINT8
Fieldbus input byte 1 feedback
20
Out
UINT8
Fieldbus input byte 2 feedback
21
Out
UINT8
Fieldbus input byte 3 feedback
22
Out
UINT8
Probe status byte 0
23
Out
UINT8
Probe status byte 1
24
Out
UINT8
Probe status byte 2
25
Out
UINT8
Probe status byte 3
26
Out
UINT8
OSSD status byte 0
27
Out
UINT8
OSSD status byte 1
28
Out
UINT8
OSSD status byte 2
29
Out
UINT8
OSSD status byte 3
1
Direction from the Mosaic point of view

Table of Contents

Other manuals for Reer Mosaic Series

Related product manuals