EasyManua.ls Logo

Reflex Servitec 60 - Controller; Configuring Settings in the Controller; Customer Menu

Default Icon
26 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control
ler
18
— English Servitec 35-95 with
Touch controller
— 18.12.2019 - Rev. A
9 Controller
9.1 Configuring settings in the controller
You can configure the controller settings regardless of the currently selected and
active operating mode.
9.1.1 Customer menu
9.1.1.1 Customer menu – overview
Use the Customer menu to correct or determine system-specific values. In the
course of initial commissioning, the factory settings must be adjusted for the
system-specific conditions.
Note!
For a description of the operation,
see chapter 7.4 "Operator panel" on
page 13 .
A three-digit PM code is assigned to the setting options
PM
code
Description
001 Select the language
002 Set the time
003 Set the date
004 Select the system type
• Levelcontrol
• Magcontrol
005
Set the P
0
minimum operating pressure, see chapter 7.2 "Setting the
minimum operating pressure for Magcontrol" on page 13 .
006 Set the actuating pressure for the system safety valve.
– The actuating pressure protects the device.
Degassing
˃
012 • Degassing programme
• Continuous degassing
• Interval degassing
• Run-on degassing
013 • Continuous degassing time
Make-up >
023 • Maximum make-up time …min.
024 • Maximum make-up cycles … /2 h.
• Frequency of make-up cycles in 2 hours.
024 • Make-up pressure
– Standard = Make-up pressure ˃ 2.3 bar.
– Setting range 1.3 – 2.3 bar.
– < 1.3 bar.
027 • With contact water meter "Yes/'No".
– If "Yes", continue with 028.
– If "No", continue with 007.
028 • Reset make-up quantity "Yes/No".
– If "Yes", reset to "0".
029 • Maximum make-up quantity ... l
030 • Water treatment "Softening / Desalination / None".
– If "Softening", continue with 031.
– If "Desalination", continue with the next point
– If "None", continue with 007.
With conductivity monitoring "Yes/'No".
031 • Shut off make-up "Yes/No" (if water capacity is exhausted).
032 • Soft water capacity ... l
– Calculation required before input.
• Fillsoft I + softening:
Soft water capacity = 6000 l / hardness reduction.
• Fillsoft I + desalination:
Soft water capacity = 3000 l / hardness reduction.
• Fillsoft II + softening:
Soft water capacity = 12000 l / hardness reduction.
• Fillsoft II desalination:
Soft water capacity = 6000 l / hardness reduction.
PM
code
Description
033 • Hardness reduction … °dH = GHactual – GHtarget
– Can be called when softening or desalination is active.
– Calculate the required reduction in overall hardness GH
before input.
034 • replacement interval… months (for softening cartridges
according to manufacturer).
007 Maintenance interval… months
008 Floating contact
• Message selection >
• Message selection: only messages marked with "√" are
output.
• All messages: All messages are output.
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
Information >
• Position of the "PV" 2-way motorized ball valve at the pressure
side of the pump.
– Position in %
• Software version
9.1.1.2 Setting the customer menu - "Time" example
The setting of system-specific values is explained below using the setting of the
time as example.
To adjust the system-specific values, proceed as follows:
1. Press "Settings".
– The controller switches to the setting area.
2. Press "Customer >".
– The controller opens the Customer menu.
3. Press the required area.
– The controller switches to the selected area.
– Use the scroll bar to navigate through the list.

Table of Contents