Installation
12 English
Variomat Touch 09.2020 - Rev. A
The "LIS" level sensor uses a pressure load cell. This pressure pick-up is to be
installed after the primary vessel has been placed at its final position, see
chapter 7.3.3 "Tank installation" on page 10 . Comply with the following
instructions:
Remove the transport securing device (squared timber) at the vessel base
of the primary vessel.
Replace this transport securing device with the pressure load cell.
In the case of a vessel volume of 1000 l (Ø 1000 mm) or more, use
the supplied screws to attach the pressure load cell at the vessel
base of the primary vessel.
Avoid shock-type loading of the pressure load cell by, for example,
subsequent alignment of the vessel.
Use flexible hoses to connect the primary vessel and the first secondary
vessel.
Use only the supplied connection sets, see chapter 7.3.3 "Tank
installation" on page 10 .
Perform a null balancing of the filling level when the primary vessel is
aligned and fully emptied, see chapter 8.6 "Parametrising the controller in
the Customer menu" on page 17 .
Standard values for level measurements:
Primary vessel
Measuring range
200 l
0 4 bar
300 500 l
0 10 bar
600 1000 l
0 25 bar
1500 2000 l
0 60 bar
3000 5000 l
0 100 bar
7.4 Switching and make-up variants
7.4.1 Function
The current filling level is recorded in the primary tank by the "LIS" level sensor
and evaluated in the controller. The value for the minimum filling level is
specified in the controller's Customer menu. If the level drops below the defined
minimum, the "WV" make-up valve opens and fills the primary tank.

Note!
To complete the make-up function from the drinking water system,
Reflex offers the Fillset with integrated system separator and Fillsoft
softening equipment, see chapter 4.6 "Optional equipment and
accessories" on page 5 .
7.4.1.1 Using a single-tank system
1
Heat generator
2
"MAG" expansion vessel
3
Primary vessel
4
Control unit
5
Reflex Fillset
ST
Dirt trap
WC
Make-up pipe
PIS
Pressure transducer
WV
Make-up solenoid valve
EC
Degassing line
For gas-rich water from the system.
For degassed water into the system.
LIS
Level sensor
Single boiler system ≤ 350 kW, water temperature < 100 °C.
Connect the Reflex Fillset with integrated system separator upstream when
using mains water for make-up.
If you don't connect a Reflex Fillset upstream, use an "ST" dirt trap with a
mesh size ≥ 0.25 mm for the make-up.

Note!
The quality of the make-up water must comply with the applicable
standards such as VDI 2035.
If you cannot achieve this quality, use the Reflex Fillsoft to soften
the make-up water from the mains water network.
7.4.1.2 Using a district heating substation
1
District heating house substation
2
Primary vessel
3
"MAG" expansion vessel
4
Site-provided make-up unit
5
Control unit
WC
Make-up pipe
PIS
Pressure transducer
WV
Make-up solenoid valve
ST
Dirt trap
EC
Degassing line
For gas-rich water from the system.
For degassed water into the system.
LIS
Level sensor
District heating water is particularly suitable as make-up water.
Water treatment is not necessary.
Use an "ST" dirt trap with a mesh size ≥ 0.25 mm for the make-up.

Note!
You require the approval of the district heating water supplier.

Table of Contents

Other manuals for Reflex Variomat Touch VS 2-1/60

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reflex Variomat Touch VS 2-1/60 and is the answer not in the manual?

Reflex Variomat Touch VS 2-1/60 Specifications

General IconGeneral
BrandReflex
ModelVariomat Touch VS 2-1/60
CategoryControl Systems
LanguageEnglish

Related product manuals