Controller
20 English
Variomat Touch 09.2020 - Rev. A
A three-digit PM code is assigned to the setting options
PM
Code
Description
001
Select the language
002
Set the time
003
Set the date
Execute null balancing
The primary vessel must be empty
The system checks whether the signal from the level sensor
matches the selected primary vessel.
005
Set the minimum operating pressure P
0
, see chapter 8.2 "Variomat
switching points" on page 15 .
Degassing >
010
Degassing programme
No degassing
Continuous degassing
Interval degassing
Run-on degassing
011
Continuous degassing time
Make-up >
023
Maximum make-up time …min
024
Maximum make-up cycles /2 h
027
With water meter "Yes/'No"
If "Yes", continue with 028
If "No", continue with 007
028
Make-up quantity (Reset) "Yes/No"
If "Yes", reset to "0"
029
Maximum make-up quantity ... l
030
Softening "Yes/'No"
If "Yes", continue with 031
If "No", continue with 007
007
Maintenance interval… months
008
Floating contact
Message selection >
Message selection: only messages marked with "√“
are output.
All messages: All messages are output.
015
Change remote data "Yes/No”
Fault memory > History of all messages
Parameter memory > History of parameter input
Display settings > Brightness, screen saver
009
Brightness … %
010
Screen saver brightness … %
011
Screen saver delay …min
018
Secure access "Yes/No"
Information >
Vessel
Volume
Weight
Diameter
Position
Position in %
Software version
10.3.1.2 Setting the customer menu - "Time" example
The setting of system-specific values is explained below using the setting of the
time as example.
To adjust the system-specific values, proceed as follows:
1. Press "Settings".
The controller switches to the setting area.
2. Press "Customer >".
The controller opens the Customer menu.
3. Press the required area.
The controller switches to the selected area.
Use the scroll bar to navigate through the list.
4. Set the system-specific values for the individual areas.
Use the "Left" and "Right" buttons to select the display value.
Use the "Up" and "Down" buttons to change the display value.
Confirm your entries with "OK".
Press "i" to display a help text for the selected area.
Press "X" to cancel your input without saving the new settings. The
controller automatically opens again the list.
10.3.2 Service menu
This menu is protected with a password. It can be accessed only by the Reflex
Customer Service.
10.3.3 Default settings
The device controller is shipped with the following default settings. Use the
Customer menu to adjust these values to local conditions. In specific cases, it is
possible to further adjust the values in the Service menu.

Table of Contents

Other manuals for Reflex Variomat Touch VS 2-1/60

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Reflex Variomat Touch VS 2-1/60 and is the answer not in the manual?

Reflex Variomat Touch VS 2-1/60 Specifications

General IconGeneral
BrandReflex
ModelVariomat Touch VS 2-1/60
CategoryControl Systems
LanguageEnglish

Related product manuals