Controller
Master/Slave Operation — 24.09.2015 English — 17
15. Specify the value for the maximum pressure deviation for the
device.
This parameter is meaningless in the master and can be
ignored.
Define the parameter in the slaves.
Setting range 0.1 – 5.0 bar.
Use the buttons to enter the parameter value.
Press "OK" to confirm.
Settings>Service>Master/Slave
(243) Max. pressure deviation
1.0
2.9 bar 0 %
16. Press "Activation delay“.
The activation delay determines the activation
behaviour of the optional second pump, compressor or
overflow valve.
Settings>Service>Master/Slave
(244) Activation delay 5s
(245) Max. level deviation 5%
(246) Block message 29 PFK? No
2.9 bar 0 %
17. Specify the value for the activation delay for the device.
This parameter is meaningless in the master and can be
ignored.
Define the parameter in the slaves.
Setting range 0 – 240 seconds.
Use the buttons to enter the parameter value.
Press "OK" to confirm.
Settings>Service>Master/Slave
(244) Activation delay
_5s
2.9 bar 0 %
OK