P36-10 Zero Clearance Direct Vent Gas Fireplace | 11
|
11
installation
Min. 6"
(152mm)
30-1/2" (775mm)
Top of Unit
Min. 32" (1016mm)
to Ceiling"
CLEARANCES
COMBUSTIBLE MANTEL CLEARANCES
Because of the extreme heat this fireplace emits, the mantel clearances are critical.
Combustible mantel clearances from top of unit are shown in the diagram below.
Note: A non-combustible mantel may be installed at a lower height if the framing is made of metal studs covered with a non-combustible
board.
Note: Mantel starts at 1" deep and end at 12" deep.
Note: Ensure the paint that is used on the mantel and the
facing is "heat resistant" or the paint may discolour.