Corrigo E Heating manual, revision G Chapter 9 Settings 38
Chapter 9 Settings
In this menu group all settings for all activated functions should be available. Depending on what
choices have been made during configuration, some of the alternatives in this menu group may not
be shown.
Settings
Control temp Æ
Control pressure Æ
Alarm settings
9.1 Control temp
9.1.1 HS1, HS2 and HS3
Control parameters for the three heating system controllers.
HS1
P-band: 100.0 °C
I-time: 100.0 sec
9.1.2 HWC1 and HWC2
Control parameters for the two hot water controllers.
HWC1
P-band: 100.0 °C
I-time: 150.0 sec
D-time: 1.0 sec
9.2 Control pressure
9.2.1 Control pressure
Control parameters for pressure control. Only accessible if pressure control has been configured.
Pressure control
P-band: 25.0 kPa
I-time: 100.0 sec
Min.output: 0%
9.3 Alarm settings
Alarm settings
Alarm limits Æ
Alarm delay Æ