Corrigo E Heating manual, revision G Chapter 10 Time settings 41
Chapter 10 Time settings
General
Corrigo has a year-base clock function. This means that a week-schedule with holiday periods for a
full year can be set. The clock has an automatic summer- winter-time changeover.
Individual schedules for each week-day plus a separate holiday setting. Up to 24 individual holiday
periods can be configured. Holiday schedules take precedence over other schedules.
Each day has up to two individual running periods. For two-speed fans and pressure controlled fans
there are daily individual schedules for normal speed and reduced speed , each with up to two
running periods.
Up to five separate digital timer outputs can be configured. Each with individual week-schedules
with two activation periods per day. These outputs can be used to control lighting, doorlocks etc.
Time/Date Æ
HS1 Night setback Æ
HS2 Night setback Æ
HS3 Night setback Æ
HWC1 Night setback Æ
HWC2 Night setback Æ
Timer output1 Æ
Timer output2 Æ
Timer output3 Æ
Timer output4 Æ
Timer output5 Æ
Holidays Æ
10.1 Time / Date
This menu shows and permits the setting of time and date.
Time is shown in 24 hour format.
Date is shown in the format YY:MM:DD.
Time: 18:21
Date: 04:02:23
Weekday: Monday
10.2 HS_ Night Set-back
HS1 Night Setback
On Æ
5.0 room-degrees
Setting comfort temperature periods.
For each control system there are 8 separate setting menus, one for each weekday and one extra for
holidays.
Holiday schedules take precedence over other schedules.
For 24 hour running, set a period to 00:00 – 24:00.
To disable a period, set it to 00:00 – 00:00.
HS1 Comfort time
Monday
Per 1: 07:00 – 16:00
Per 2: 00:00 - 00:00