Corrigo E Heating manual, revision G Chapter 11 Actual / Setpoint 43
Chapter 11 Actual / Setpoint
In this menu group all actual current values and setpoint values are displayed and, providing a
sufficiently high log on level is used, all setpoints can be changed.
The following menus are available providing that the corresponding input is activated.
11.1 Setpoint Heating systems HS1, HS2 and HS3
Outdoortemp: 18.4°C
HS1
Act.: 19.8°C SetpÆ
Setp: 20.0°C
Submenu: Setpoint
In-between-values are calculated using straight lines between breakpoints. Setpoints for
temperatures lower than the lowest breakpoint and higher than the highest breakpoint are calculated
by extending the line between the two last breakpoints at either end. Example: At the lower end the
setpoint is increasing by 14°C for every 5 °C lowering of the outdoor temperature. So the setpoint at
–23°C would be 77+3/5 * 14°C = 85.4°C.
Outd. comp. setp.HS1
-20 °C = 77 °C
-15 °C = 63 °C
-10 °C = 59 °C
Outdoor comp. setp.
-5 °C = 54 °C
0 °C = 53 °C
5 °C = 43 °C
Outdoor comp. setp.
10°C = 35 °C
15°C = 25 °C
11.2 Room sensor HS1, HS2 and HS3
Room sensor HS1
Actual: 20.8°C
Setpoint: 21.0°C
Return temp: 20.0°C
11.3 Return water temperature
Return temp.
HS1: 20.0°C
HS2: 24.0°C
HS3: 23.0°C