Corrigo E Heating manual, revision G Chapter 9 Settings 40
9.3.2 Alarm delays
Control deviation, HS1, HS2 and HS3
Control deviation
HS1: 60 min
HS2: 60 min
HS3: 60 min
Control deviation HWC1 and HWC2
Control deviation
HWC1: 60 min
HWC2: 60 min
Scalding limit
Scalding
HWC1: 300 sec
HWC2: 300 sec
Boiler limits
High boiler temp
0 sec
Low boiler temp
0 sec
Expansion vessel / External alarm
Expansion vessel
60 sec
External alarm
60 sec