Corrigo E Heating manual, revision G Chapter 2 About Corrigo E 7
CE-marking
Conforms with the EMC standards: CENELEC EN61000-6-3:2001, CENELEC EN61000-6-
1:2001.
Inputs
Analogue inputs AI..............................................Settable 0…10 V DC or PT1000, 12 bit A/D
Digital inputs DI.......................................................................................Potential free closure
Universal inputs UI...........................................Can be set to act as either an analogue input or
a digital input with specifications as above
Outputs
Analogue outputs AO.......................................................Settable 0…10 V DC; 2…10 V DC;
10…0 V DC or 10…2 V DC
8 bit D/A short-circuit protected
Digital outputs DO ..................................................Triac outputs, 24 V AC, 0.5 A continuous
Options
LON...................................................................FT3150, gives a second communication route
TCP/IP..................................................Replaces RS485 for EXOline (Port 1) communication
External hand terminal, E-DSP ...........................For use with Corrigo E units without display
Position of the terminals on Corrigo E