20
Manual CORRIGO U-SERIE 2002-09
Konfigurering, snabbmetod
At the top of the configuration branch there are two menues, Configuration code 1
and Configuration code 2.
Each position in the code corresponds, in order, to hte menues A to V described on
the previous pages.
The codes may be set directly in these two menues.
Tables for configuration code
There is also a special table to facilitate the choice of configuration code. This is
always supplied together with the C
ORRIGO instruction sheet.
Control HS1
In this menu branch you can look at and set most control values for the temperature
control of HS1.
See also the menu branch Settings.
Which of the menues below that will be shown and which will be settable depends on
the configuration and the present login level. The table shows all the menues.
1 Setpoint / Actual temp/Output.
Output is only shown if HS1 is configured with 1 sequence. When HS1 is
configured as 3-point , output is shown as + or -.
2 HS1 Y1 / Y2 Output %. Only shown if HS1 is configured with 2 sequences.
3 Manual offset / Actual setpoint.
The control curve can be offset ±30K / Setpoint including offset.
4 Setpoint Room / Actual Room / Room compensation.
Display only. Change of room temp in next menu
5 Setpoint Room.
6 Running mode / Actual night reduction
7 Night reduction / Standby reduction
Setting of reduction of room temperature in degrees.
If no room sensor is installed the lowering in water temperature is calculated
using the given K-factor. See under Settings.
8 Control curve. Breakpoint 1.
9 Control curve. Breakpoint 2.
10 Control curve. Breakpoint 3.
11 Control curve. Breakpoint 4.
12 Control curve. Breakpoint 5.
13 Control curve. Breakpoint 6.
14 Control curve. Breakpoint 7.
The breakpoints must be placed with 1 at the
lowest and 7 at the highest outdoor tempera-
ture.
State the outdoor temperature and outgoing
water temperature for each point.
Outdoor temperatures lower than that given for
point 1 will give a water temperature equal to
that at point 1.
Outdoor temperatures higher than that given for
point 7 will give a water temperature equal to
that at point 7.
4
5
6
7
Water temperature
Outdoor temperature
3
2
1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Regin Corrigo U10 Series and is the answer not in the manual?

Regin Corrigo U10 Series Specifications

General IconGeneral
BrandRegin
ModelCorrigo U10 Series
CategoryController
LanguageEnglish

Related product manuals