22
Manual CORRIGO U-SERIE 2002-09
AO Analogue out
In this menu branch you can look at the configuration and output of the analogue
outputs.
AO1 Control valve for heating sequence 1, HS1-CV1. Only shown if HS1-CV1-type
is configured as 0...10 V DC (See Configuration point K)
AO2 Control valve HW-CV1 if THW is configured as 1 sequence or
Control valve THW-CV1 if THW is configured as 2 sequences.
AO3 Control valve TVV-SV1 if THW is configured as 1 sequence or
Control valve TVV-SV2 if THW is configured as 2 sequences.
AO4 Control valve HS2-CV1. CORRIGO U20 only. Only shown if HS2-CV1-type is
configured as 0...10 V DC (See Configuration point O)
AO5 Control valve HS1-CV2. Only shown if HS1 is configured as 2 sequences.
(See Configurarion point L)
AO6 Control valve HS2-CV2. Only shown if HS2 is configured as 2 sequences.
(See Configurarion point P)
DO Digital out
In this menu branch you can look at the status for the digital outputs.
DO1 Control pump HS1
DO2 3-point output HS1 increase. Only shown if HS1-CV1-type is configured as 3-
point (See Configuration point K)
DO3 3-point output HS1 decrease. Only shown if HS1-CV1-type is configured as 3-
point (See Configuration point K)
DO4 Control pump HS2. CORRIGO U20 only.
DO5 3-point output HS2 increase or Timer output TO1. CORRIGO U20 only.
DO6 3-point output HS2 decrease or Timer output TO2. CORRIGO U20 only.
DO7 Potential-free relay for alarm output. 1 A, 24 V AC/DC. Closes on alarm.
Setting outputs manually
Both digital and analogue outputs can be set to manual mode for testing and for
temporary running.
1. Analogue outputs
To set to manual mode press ! and change to HAND using or .
Then press OK and confirm, then change the output value using the arrow
buttons. Confirm the setting using OK.
To revert to normal running mode press again and change to AUTO using
or . Confirm using OK.
If the setting is not reset to the AUTO mode within 15 seconds, an alarm will
be activated.
2. Digital outputs
To set to manual mode press and change to the desired mode ON or OFF
using or . Then press OK and confirm.
To return to normal running mode press again and change to AUTO using
or . Confirm using OK.
If the setting is not reset to the AUTO mode within 15 seconds, an alarm will
be activated.