Temperature
Here you can view all actual and setpoint values for temperature control. The menu is visible
to all users, regardless of log on level. However, to make changes you need at least Operator
authority.
Only menus for activated functions will be shown.
Setpoint Supply air temperature control
Here, actual and setpoint values are shown, as well as
the outdoor temperature if a outdoor sensor has been
configured. This is a read-only menu. No settings can be
made here.
Submenu: Setpoint.
Setpoint Outdoor temperature compensated Supply air control
Here, actual and setpoint values are shown, as well as
the outdoor temperature if a outdoor sensor has been
configured. This is a read-only menu. No settings can be
made here.
Submenus: Setpoint
In control modes Supply air control/Room control and Supply air control/Extract air control ,
the setpoint relationship is used when supply air control is active.
Use the eight breakpoints to generate a setpoint /
outdoor temperature relationship.
In-between-values are calculated using straight
lines between breakpoints.
Setpoints for temperatures lower than the lowest breakpoint and higher than the highest
breakpoint are calculated by extending the line between the two last breakpoints at either
end.