EasyManua.ls Logo

Regin Corrigo - Support Control Heating;Support Control Cooling; Frost Protection Temperature

Regin Corrigo
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fel! Använd fliken Start om du vill tillämpa heading 1 för texten som ska visas här. Corrigo ventilation user
guide, revision F
14
This function operates according to the
assumption that one may accept a slightly higher
indoor temperature when it is warm outside and
vice versa, providing an excellent opportunity for
conserving energy.
Support control heating/Support control cooling
Support control is normally used when room temperature
control or extract air control has been configured, to
prevent a too large offset in temperature when the unit is
“Off”.
“Support control Heating” or “Support control Cooling
will run if support control is configured, the running
mode is "Off" (timer control OFF and not in extended
running) and if conditions call for support control.
Minimum run time is settable 0 to 720 minutes (FS= 20 minutes).
Frost protection temperature
Relevant value for the water temperature at the frost
protection sensor. Frost protection can be set to function
either on Y1, Y4 or on both. The function only supports
a single sensor.
Outdoor comp setp
-20.0°C = 25.0°C
-15.0°C = 24.0°C
-10.0°C = 23.0°C
Outdoor comp setp
-5.0°C = 23.0°C
0.0°C = 22.0°C
5.0°C = 20.0°C
10.0°C = 19.0°C
20.0°C = 18.0°C
If cascade control
max/min supply setp
Max: 30.0°C
Min: 12.0°C
Support heating
Room temp for
Start: 15.0°C
Stop: 21.0°C
Support cooling
Room temp for
Start: 30.0°C
Stop: 28.0°C
Frost protection
Actual: 30.9°C

Related product manuals