Fel! Använd fliken Start om du vill tillämpa heading 1 för texten som ska visas här. Corrigo ventilation user
guide, revision F
18
Submenu Extra compensation. A
temperature dependent compensation
similar to the one above but with
selectable temperature source.
Manual frequency control SAF (there are also corresponding menus for
EAF)
Here, Actual and Setpoint values are displayed. This is a read-
only menu. No settings can be made here.
Submenu Setpoint values for normal speed (1/1)
and reduced speed (1/2).
The setpoint is set in % of the full output. 100 %
= 10 V output signal.
Submenu outdoor compensation. An outdoor
temperature dependent compensation of the
pressure setpoint value can be added.
The compensation can be set for either the supply air fan alone or for both fans.
Submenu extra compensation. A
temperature dependent compensation
similar to the one above but with
selectable temperature source.
Frequency control external
For fan control using an external control signal, e.g. via a VAV
optimizer.
Comp sens:Room temp1
15 °C = 0 m3/h
20 °C = 0 m3/h
25 °C = 0 m3/h
manual SAF
Output: 75%
Frequency control
manual SAF
Output 1/1: 75%
Output 1/2: 50%
Outdoor comp output
-20 °C = -40 %
10 °C = 0 %
Act comp: 0 %
15 °C = 0 %
20 °C = 0 %
Frequency Control
manual SAF
Output: 0 %
Outdoor comp outp
-20 °C = -40 %
10 °C = 0 %
Act comp: 0 %
15 °C = 0 %