EasyManua.ls Logo

Rehau Ba - Connecting Thermal Actuators (TH 1 - TH 8); External Switch;Timer

Rehau Ba
69 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
THERMAL ACTUATORS 24V
L N L L L L LN N N N N
OUT PUT 1
L N L L L L LN N N N N
THERMAL ACTUATORS 24V
L LN N
L LN N
Out put 2 Out put 3 Out put 4 Out put 5 Out put 6 Out put 7 Out put 8
OUT PUT 1 Out put 2 Out put 3 Out put 4 Out put 5 Out put 6 Out put 7 Out put 8
ZONE 1 ZONE 4
BA Master Controller
THERMAL ACTUATORS
1 2 3 4 5 6
L N L L L L LN N N N N
1 2 3 4 5 6
L N L L L L LN N N N N
THERMAL ACTUATORS
7 8
L LN N
7 8
L LN N
SWITCH
EXT.
I O
+ +
TT
LINK
DISPLAY
L YN X
SUPPLY
SENSOR
THERMOSTAT BUS
+
T
+
T
APP
SENSOR
THERMOSTAT BUS
MIXING VALVE
0 - 10V
MIXING VALVE 24V AC
+
T
ON
OFF
1 2 3
4 5
6
7
8
C
B
A
9
8
7
6
5
4
3
2
1
0
F
E
D
7
6
5
4
3
2
1
0
9
8
STRING
NUMBER (1-F)
UNIT
NUMBER (1-9)
DIP SWITCH
SUPPLY
230VAC
BOILER
B1 B2
X-RELAY SEC. PUMP
230VAC
LL NN
C1 C2
28. Actuator connection to Master Controller
29. Connection of external switch/ timer located on the Master Collection
TIMER. EXTERNAL SWITCH
VOLT FREE
CONTACTS
5.2.5 Connecting Thermal Actuators (TH 1 – TH 8)
Maximum 14 x 24 Volt actuators per controller.
Ensure that the actuators are connected to the correct zone.
Actuators controlled by zone 1 must be connected to output
terminal 1 (TH 1) etc.
Connect one wire from the actuator to right hand terminal on the
respective zone output terminal block (TH 1-TH 6) then connect the
other wire from the actuator to the left hand terminal block. These
terminal blocks are not polarity sensitive.
A maximum of 4 actuator heads can be installed into each
output, 2 terminal blocks, 14 actuator max. per controller
within the controller as long as they are to be controlled by
the same sensor.
5.2.6 External Switch/Timer
The controllers can accept a volt free signal from an external switch /
timer which will facilitate the switching between day mode and night
set back mode only. For setback the switch will be in OPEN circuit and
CLOSED for day- time operation. Each controller type comes fitted
with a link across the Ext switch. This link has to be removed and
replaced with the switch/timer connection all other system parameters
will have to be programmed into either a REHAU CT2 Programmable
Room Sensor. No system programming is available with the REHAU BA
controller. (See section 8.1 System Start Up & Operating Instructions).
Connection of the external switch/timer will override the
settings of any CT2 Programmable Room Sensors installed onto
the system.

Table of Contents