43
SYSTEM START UP AND OPERATING
INSTRUCTIONS
REHAU BA MASTER CONTROLLER
8.0
8.2
The BA Master Controller comes with pre-set temperatures,
these pre-set values are fixed so the REHAU BA Master Controller
should always be used in conjunction with at least one REHAU
CT2 Programmable Room Sensor.
However if a REHAU CT2 Clock sensor is fitted to the system it will
override the fixed and the programmed parameter set in the REHAU
BA Master Controller.
Default Settings
The BA Master Controller has the following default
temperature settings:
Description Factory settings
Day temperature 21°C
Night temperature 18°C
Off Temperature (Frost protection) 5°C
Floor Limit temperature, high 27°C
Floor Limit temperature, low 17°C
BA Master Controller controls only temperature settings and
there is no time control. If a REHAU CT2 Clock Thermostat is
NOT fitted on the system an external time clock will be required
to control the time switching of the system.
The REHAU BA Master Controller can accept a volt free signal from
an external switch (timer) which will facilitate the switching between
day mode and night set back mode. For setback the switch will be in
OPEN circuit and CLOSED for day- time operation. Each controller type
comes fitted with a link across the TIME terminal. This link has to be
removed and replaced with the switch/timer connection.