A-1
Error Messages
APPENDIX A
Error Messages
The following shows the error messages to be displayed on the PSC Console.
When such error messages appear, take the corrective actions in accordance with
the following instructions.
A.1 Error Message: TRANSFER FAILED
Causes
A communication error occurred when the PSC Console was connected to or
disconnected from the PSC3000/PSC4000/PSC5000 System.
Tasks do not run.
Corrective Actions
Press the ALLCLR key.
Verify that tasks are in "RUN" state.
If the tasks are not in "RUN" state, execute the tasks.
Important: To execute tasks, use the Programming Terminal. For operation of the
Programming Terminal, refer to the operation manual of the PSC3000,
PSC4000 or PSC5000 Programming Terminal (IM 23004, IM 23016 or
IM 23013).
A.2 Error Message: TOO LARGE !
Causes
The attribute data number is too large.
Corrective Actions
Press the DATA key to allow the PSC Console to enter the number.
Enter the correct number (between 0 and 499).

Table of Contents