EasyManua.ls Logo

Remak VCS - Page 103

Remak VCS
118 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
101
Control units VCS
PLC Controller for Compressor Output Control
Viewing Alarms
If a failure occurs during operation, this state is signalled by
a flashing symbol . Furthermore, the corresponding alarm
can be displayed. For a description, refer to point 5.2.
Alarm Types
Application Version Settings
One compressor with output
control, BASIC version
-1
Two compressors, BASIC version - 2
One compressor without output
control, PREMIUM version
1
Two compressors, PREMIUM version 2
Code Cause Description
A-01
LP sensor
failure
Check 4-20mA current loop.
A-02
Td sensor
failure
Check the tempera-
ture sensor.
A-03
HP sensor
failure
Check 4-20mA current loop.
A-04
Compressor
1 failure 1
Check the compres-
sor protections.
A-05
Compressor
2 failure
Check the compres-
sor protections.
A-06 HP failure
Number of HP pressostat
failures exceeded.
A-07 LP failure
Number of LP pressostat
failures exceeded.
A-08
Control sig.
failure
Check 0-10V signal.
A-09
Expanding
module failure
Expanding module
does not respond.
A-10 EEV failure Expansion valve failure.
A-11
Condenser
failure
Check the condenser
circuit breaker.
n P-17 Coolant: Used coolant type.
(0= R404A, 1=R22,2=R744, 3 = R290, 4 = R134A,
5 = R407C, 6 = R410A, 7 = R427A, 8 = R507A).
n P-32 PID HP Udz: PID control upper insensitive zone.
n P-33 PID HP Ldz: Control lower insensitive zone
n P-34 PID HP Bp: Control proportionality zone
n P-35 PID HP Ti: Control integration constant
n P-36 PID HP Td: Control derivative constant
n P-37 PID HP Arw: Control anti-reset li
n P-38 PID HP Speed: Maximum number of PID output
changes per 1 sec.
n P-40 Bypass time LP: Low-pressure pressostat
bypass time upon compressor start.
n P-41 Filter time LP: Low-pressure pressostat bypass
time when the compressor is running.
n P-42 Bypass time LPA: Low-pressure sensor failure
bypass time upon compressor start.
n P-43 Filter time LPA: Low-pressure sensor bypass
time when the compressor is running.
n P-45 Curb Enable: Output limitation enable from the
PID high-pressure controller.
n P-47 Warning time (0 to 600 sec):
Time for which the output limitation is signalled.
n P-50 PID Cond Bp: PID control proportionality zone.
n P-51 PID Cond Ti: Control integration constant
n P-52 PID Cond Td: Control derivative constant
n P-53 PID Cond Udz: PID control upper insensitive
zone.
n P-54 PID Cond Ldz: PID control lower insensitive zone
n P-55 PID Cond Speed: Maximum number of PID
output changes per 1 sec.
n P-56 PID Cond Arw: Control anti-reset li.
n P-48 Warning value (0 to 100%):
PID controller limiting value – when exceeded, the output
limitation is signalled.
n P-60 Increment time (10 to 600 sec):
Additional compressor connection time.
n P-61 Decrement time (0 to 120 sec):
Additional compressor switch-off delay time.
n P-66 Dif. through En.: Enables use of the differential
pressostat information for the cooling heat exchanger.
Anti-freeze protection. It starts defrosting.
n P-67 Swap time: Cooling/heating mode
switching time.
n P-68 Det time: Maximum defrosting time.
n P-69 Dit time: Defrosting interval.
n P-70 Switch OFF:
e compressor is switched off when switching
cooling/heating modes.
n P-71 Switch Cap.: (0 to 100%)
Compressor output between cooling/heating
mode switching.
n P-74 Defrost LP: (-10.0 to 2.5°C)
Evaporation pressure limit compared with S-00 below
when defrosting is enabled.
n P-77 Maf:
Number of cycles for the pressure oscillation mathematical
filter.
n P-79 App: Application selection.