43
Control units VCS
898 A 898 A Displayed time format - 12h/24h 0 24 h
1 12 h
Passwords
899 S 899 S Password for Service level access 0 9999
901 A 901 A Password for Admin level access 0 9999
902 U 902 U Password for User level access 0 9999
903 G 903 G Password for Guest level access 0 9999
Comunication with Building management system
(BMS) - (Aer settings - reset required !!)
LON
921 S 921 S Send heart beat (s) 2700 0 9999 s
922 S 922 S Receive heart beat (s) 3600 0 9999 s
923 S 923 S Min send intervall (s) 5 0 9999 s
924 S 924 S Service pin 0 inactive
1 active
925 S 925 S Out temperature value 0 of application 0
1 of communication
926 S 926 S Fire alarm (external) 0 of application 0
1 of communication
Modbus RTU - Slave (BMS)
925 S 925 S Out temperature value 0 of application
1 of communication
926 S 926 S Fire alarm (external) 0 of application
1 of communication
931 S 931 S Modbud Slave1 0 inactive
1 active
932 S 932 S Address Slave1 1
933 S 933 S Baud rate Slave1 default 9600 b/s
2400 (factor 10)
4800 (factor 10)
9600 (factor 10)
19200 (factor 10)
38400 (factor 10)
934 S 934 S Stop bits Slave1 0 One stop bit 1
1 Two stop bits
935 S 935 S Parity Slave1 0 Even 2
1 Odd
2 None
936 S 936 S Termination (resistor) Slave1 0 inactive 0
1 active
937 S 937 S Response timeout Slave1 5 0 3600 s
Menu HMI-SG
Parameter
Meaning
Factory Settings
Notation Reading Value Min Max
code level code level