72
Connection to the Master System (LonWorks Standard)
Network Variable: nvoPress02
Description: Not used
Object: SNVT_press_p
Network Variable: nvoPress_Flow00
Description: Current request for the inlet fan
Object: SNVT_ow
Remark: %, Pa or l/s
Network Variable: nvoPress_Flow01
Description: Current request for the outlet fan
Object: SNVT_ow
Remark: %, Pa or l/s
Network Variable: nvo_Flow00
Description: Inlet air-ow
Object: SNVT_ow
Network Variable: nvo_Flow01
Description: Outlet air-ow
Object: SNVT_ow
Network Variable: nvoPerc00
Description: Heater output
Object: SNVT_lev_count
Network Variable: nvoPerc01
Description: Cooling output
Object: SNVT_lev_count
Network Variable: nvoPerc02
Description: Heat exchanger output
Object: SNVT_lev_count
Network Variable: nvoPerc03
Description: Mixing output
Object: SNVT_lev_count
Network Variable: nvoPerc04
Description: Not used
Object: SNVT_lev_count
Network Variable: nvoPerc05
Description: Electric heater output
Object: SNVT_lev_count
Network Variable: nvoPerc06
Description: Inlet fan output
Object: SNVT_lev_count
Network Variable: nvoPerc07
Description: Outlet fan output
Object: SNVT_lev_count
Network Variable: nvoPerc08
Description: Not used
Object: SNVT_lev_count
Network Variable: nvoPerc09
Description: Air humidity in the inlet
Object: SNVT_lev_count
Network Variable: nvoPerc10
Description: Air humidity in the room
Object: SNVT_lev_count
Network Variable: nvoPerc11
Description: Outdoor air humidity
Object: SNVT_lev_count
Network Variable: nvoPerc12
Description: Humidication output
Object: SNVT_lev_count
Network Variable: nvoPerc13
Description: Dehumidication output
Object: SNVT_lev_count
Network Variable: nvoPerc14
Description: Electric after-heater output
Object: SNVT_lev_count
Network Variable: nvoAHum00
Description: Absolute humidity in the inlet
Object: SNVT_abs_humid
Network Variable: nvoAHum01
Description: Absolute humidity in the outlet
Object: SNVT_abs_humid
Network Variable: nvoOpMode
Description: Current device state
Object: SNVT_switch
Values: 0 Stop
1 Operation (Comfort)
2 Operation (Economy)
3 Not used
4 Optimized start
5 Night chilling
6 Temperature start-up
7 Night turn-over
8 Not used
9 Fire
10 Safety stop
11 Fan run-down
12 Start
>12 Not dened
State: 0: Inactive :Mode Auto
1: Active :Mode OS
Default: Value: 0
State: 0
Network Variable: nvoSwitch00
Description: Current fan state
Object: SNVT_switch
Values: 0 Stop
1 1St
2 2St