73
Control units VCS
Connection to the Master System (LonWorks Standard)
3 3St
4 4St
5 5St
>5 Not dened
State: 0: Inactive
1: Active
Network Variable: nvoState
Description: Alarm classes, Control mode
Object: SNVT_state_64 (64 bit)
Bits:
Bit [0 …63] Binary: *Reverse:
Alarm class - danger (A) 0 63
Alarm class - critical (A) 1 62
Alarm class - low (B) 2 61
Alarm class - warning (B) 3 60
4 59
5 58
6 57
7 56
8 55
9 54
10 53
Current control temperature - room 11 52
Current control temperature - outlet 12 51
Current control temperature - inlet 13 50
Current control humidity - room 14 49
Current control humidity - inlet 15 48
. .
. .
. .
63 0
Remark: *The bit name order can be reversed in some LON
software tools
Network Variable: nvoDO
Description: Digital outputs
Object: SNVT_state_64 (64 bit)
Bits:
Bit [0 …63] Binary: *Reverse:
Inlet damper 0 63
Outlet damper 1 62
Fire damper 2 61
3 60
Inlet Fan - Run 4 59
Inlet Fan - Stop 5 58
6 57
7 56
8 55
Outlet Fan - Run 9 54
Outlet Fan - Stop 10 53
11 52
12 51
13 50
14 49
15 48
Cooling - pump 16 47
Cooling DX, Stop 17 46
Cooling DX, 1st 18 45
Cooling DX, 2st 19 44
20 43
21 42
Heat recovery 22 41
23 40
Water heating - pump 24 39
25 38
Electric heating, Stop 26 37
Electric heating, 1st 27 36
28 35
29 34
30 33
31 32
Heat pump DO 2 32 31
33 30
34 29
35 28
36 27
37 26
Heat pump DO 1 38 25
39 24
Electric after-heating, Stop 40 23
Electric after-heating, 1st 41 22
42 21
43 20
44 19
Request for humidication 45 18
Humidier pump 46 17
47 16
48 15
49 14
Gas heating, st1 50 13
Gas heating, st2 51 12
Gas heating, Mod+ 52 11
Gas heating, Mod- 53 10
54 9
55 8
Alarm output (A failures) 56 7
Alarm output (B failures) 57 6
58 5
59 4
60 3
Request for boiler room 61 2
Water pre-heating 62 1
Electric pre-heating 63 0
Remark: *The bit name order can be reversed in some LON
software tools.
Network Variable: nvoDI
Description: Digital Inputs
Object: SNVT_state_64 (64 bit)
Bits:
Bit [0 …63] Binary: *Reverse:
0 63
External input 1 1 62
External input 2 2 61
. .
. .
. .
. .