83
Control units VCS
Bit7 Exhaust back up
Bit8 Cooling
Bit9 OverHeat Burner heating
Bit10 Heating recovery
Bit11
Bit12 Heating recovery frost
Bit13
Bit14 Heating recovery damper
Bit15 Flue-gas high temperature, heater shut down
3x0014
Alarms (Word 2)
0-65535
0-1 for each bit or counted binary
to a decimal number
Bit0 Heating pump
Bit1
Bit2 Electrical Heating
Bit3 Burner fan overrun TH
Bit4 Heat pump cooling
Bit5
Bit6 Heat pump heating
Bit7
Bit8 Extra Electrical Heating
Bit9
Bit10
Bit11 Humidification
Bit12 PreWtrHeating
Bit13 Fire Alarm (external alarm)
Bit14 Electric pre-heating
Bit15 Filter Alarm
3x0015
Alarms (Word 3)
0-65535
0-1 for each bit or counted binary
to a decimal number
Bit0 Out temperature
Bit1 Supply temperature
Bit2 Heating frost temperature
Bit3 Room1 temperature
Bit4 Room2 temperature
Bit5 Exhaust temperature
Bit6 Extract temperature
Bit7
Input register (Read) (continuation)
Connection to the Master System (ModBus Standard)
Adress Description Values/Units Remarks