Control units VCS
Connection to the Master System (ModBus Standard)
3x0078
3x0079
3x0080
3x0081
3x0082
3x0083
3x0084 Outdoor air humidity - relative %r.H.
3x0085 Outdoor air humidity - absolute `-x.y - +x.y g/kg (divider 10)
3x0086 Outdoor air humidity - enthalpy `-x.y - +x.y kJ/kg (divider 10)
3x0087 Inlet air humidity - relative %r.H.
3x0088 Inlet air humidity - absolute `-x.y - +x.y g/kg (divider 10)
3x0089 Inlet air humidity - enthalpy `-x.y - +x.y kJ/kg (divider 10)
3x0090 Room air humidity - relative %r.H.
3x0091 Room air humidity – absolute `-x.y - +x.y g/kg (divider 10)
3x0092 Room air humidity - enthalpy `-x.y - +x.y kJ/kg (divider 10)
3x0093 Dew point `-x.y - +x.y g/kg (divider 10)
3x0095 Inlet air flow rate 0 - x m3/h
3x0096 Outlet air flow rate 0 - x m3/h
3x0097 Inlet air flow rate 0 - x Pa
3x0098 Outlet air pressure 0 - x Pa
3x0099
3x0101 Air quality 0 – x ppm
3x0102
3x0104 Act heating stpt `-x.y - +x.y °C
3x0105 Act cooling stpt °C
3x0106 Act sply htg stpt °C
3x0107 Act sply clg stpt °C
3x0108 Current required value of humidity -
humidification
0 - x.y %r.H. (divider 10)
3x0109 Current required value of humidity -
dehumidification
%r.H. (divider 10)
3x0110 Current humidification required value for
cascade control
%r.H. (divider 10)
3x0111 Current dehumidification required value in
cascade control
%r.H. (divider 10)
3x0112 Act sply fan stpt 0-100% (0 - x l/s)
Input register (Read) (continuation)
Adress Description Values/Units Remarks